Aqualeak EMS-5/10

ems-01 water leak sensor alarm panel from aqualeak

The Aqualeak Environmental Monitoring System (EMS) Water Leak Detection System series, are standalone leak detection systems designed to be integrated into larger Building Management Systems (BMS) and networks.

Designed for continuous operation with minimal human intervention, the EMS series is also compatible with a wide variety of sensing technologies (sold separately) to detect the presence of water and other liquids.

The Aqualeak EMS-01 is designed to monitor for water leaks in single-zone critical areas such as Tea Points, Satellite Equipment Rooms (SERs), Main Equipment Rooms (MERs) and Server Rooms.

Sensitivity to moisture and delays to alarms may be adjusted to better tailor the system to intelligently respond to a wide range of environments, situations and user requirements.

If a leak is detected, an audible alarm is activated, an LED illuminated, and, if connected, the EMS will report its alarm status to any connected device (BMS/SMS/beacon, valve) via its volt free contacts.

DOWNLOAD EMS 01 Datasheet as PDF

BENEFITS

FEATURES

OPERATION

In operation, the EMS-01 continuously monitors the sensing equipment connected to it for both circuit integrity and the presence of water. If a leak is detected, the EMS-01 will and/or can be configured to:

EMS SERIES MODELS

In addition to the EMS-01, the Aqualeak EMS series also includes the following models:

EMS 01 TECHNICAL SPECIFICATIONS

Master Panel/EMS UnitSpecification
Dimensions146 x 86 x 69 mm - Width x Height x Depth
Weight300 Grams (0.3 Kilograms)
Supply Voltage100-240 (VAC Volts / Alternating Current) 60 Hz frequency
Motherboard Output Relay Voltage250 VAC Max.
Motherboard Output Relay Current8 Amps. Maximum into resistive load
Relay Minimum Load10 Milliamps - at 5 VDC (Volts / Direct Current)
Leader Cable Belden 9534 EIA RS-232 Multicore Cable (4 Core, 24 AWG, 0.2 mm²). Variable length
Detection Response Time1 second
Alarm (Audible)85 Decibels within 0.6 m range
Alarm (Visible)LED Indicator - Front Panel
Operating Temperature0 to +50°C (Degrees Centigrade). Ambient temperature
Operating Humidity10 to 95% Relative humidity (non-condensing) at 45°C
Operating Altitude0 to 3,000 Metres
Storage Temperature-20 to +70°C
Input channels1
Maximum Sensor Cable Length100 m (with maximum 20 probes). Use recommended yellow Sensor Cable (SCY). Also requires End of Line (EOL) terminator

EMS 01 Input Output

ItemNameNotes
1Power Fault RelayNC | NO | COM
2Sensitivity MeasureUsed with Sensitivity Adjustment
3DC Out12V / 24V Selectable Output Maximum 250mA
4Fault RelayFault Relay
Relay AbbreviationsMains Abbreviations
NO = Normally OpenLS = Live Supply
NC = Normally CloseLL = Live Loop
COM = CommonNS = Neutral Supply
NL = Neutral Loop
ES = Earth Supply
EL = Earth Loop

EMS 01 Dip Switch Settings

Switch FunctionDefault SwitchFunction Default
1Unit SounderON
2Disable Relay LatchOFF
31 Minute Alarm DelayOFF
45 Minute Alarm DelayOFF
5NOT USED
6Timed LatchOFF
7NOT USED
812/24V DC Out SelectorOFF (12V)
DOWNLOAD EMS 01 Datasheet as PDF